Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09153
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2018 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 11/19/2018 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 11/19/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please provide a hi/low drinking fountain or a point of use dispenser. Show location of floor plan. |
| 11/19/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/20/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide documents sealed by an Arizona Registrant. 2.Provide ventilation to all conditioned spaces. Show calculations for all naturally-ventilated rooms. 3. Ventilation shall be supplied continuously during operating hours. 4. Provid heating/cooling calculations to justify the new heat pumps. 5. Show how the dryer vent complies with the duct length requirements. |
| 12/20/2018 | AVAUGHN1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/20/2018 | MASHFOR1 | FIRE | REVIEW | Approved | Usage is an S-2 not M |
| 12/20/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/20/2018 | ROBERT SHERRY | WATER | REVIEW | Completed |