Permit Number: T18CM09082
Parcel: 11105040A

Address:
3138 N DODGE BL

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM09082
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2018 MARTIN BROWN FIRE REVIEW Approved
12/17/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/26/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheets C-1, C-4, G-1. These plans show a 500 watt floodlight in the equipment area. Assign a branch circuit that is also shown in the panel schedule, and show the wiring methods utilized for installing the luminaire that complies with the 2011 or 2017 NEC.
#2. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for all exterior lighting on this parcel. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd.
#3. Provide a grounding detail or show how the electrical service is to be grounded. Include conductor sizes and types. If the Service is connected to the Ground Ring, please show this in the grounding detail.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.
12/28/2018 AMARTIN1 COMMUNICATIONS REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/28/2018 AMARTIN1 OUT TO CUSTOMER Completed