Review Details: REVISION - - 1ST

Permit Number - T18CM09065
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Deferred submittals must follow the requirements of the IBC Section 107.3.4.1. The submittal has the structural stamp of Scott D. Duecker, but it is not clear if he is the engineer of record for this project. If not, that engineer must review and approve these drawings per the IBC Section noted above.
In addition, please include with the deferred submittal a copy of the structural sheet indicating the framing shown in the deferred submittal.