Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM09065
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/21/2018 | MASHFOR1 | FIRE | REVIEW | Approved | |
11/28/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G.1; Code Review (Occupant Load): The Customer Waiting/Service Counter areas occupant load was based on 100 SF/occupant. These areas should be assessed as assembly areas using 15 SF/occupant. Please verify and revise as required. 2. Sheet G.1; Code Review: Please provide on this sheet the required plumbing fixture calculations per the IBC Table 2902.1. 3. Sheet G.1; Code Review: The drawing indicated the maximum allowed/provided exit travel distance is 75'/55'. Per the IBC Table 1014.3, the maximum allowable common path of egress travel is 100 feet. Per the IBC Table 1016.2, the exit access travel distance is 250 feet. Please add a plan to the drawings indicating the actual exit access travel distance and the number of occupants using each exit. Use the IBC Section 1016.3 for the measurement criteria. 4. Sheet A.1; Wall Schedule: Please provide a detail of the fire resistant rated W6, and include the U.L. Listing Number for that wall. 5. Sheet A.1; Keynotes: Note 1 references Details 1/A.5 and 2/A.5 for interior partitions. Is 2/A.5 correct? Please verify. 6. Sheet A.1; Keynotes: Note 21 references a recess in the floor slab for an alignment rack. Please provide a detail for that recess slab, or include in a note on Sheet G.1 for Deferred Submittals. 7. Sheet A.1; Keynotes: Note 12 references a hoist. Please provide a detail for the hoist structure and foundation, or include the information in a note on Sheet G.1 for Deferred Submittals. 8. Sheet A.1; Keynotes: Note 15 references a steel roof hatch and access ladder. Please indicate in that note to see Sheet A.3. 9. Sheet A1.1; Mounting Heights: Please reference Sheet A.7 for the restroom grab bar locations per the ICC/ANSI Figures 604.5.1 and 604.5.2. 10. Sheet A.2; Notes: A stucco note references Section D/A3.1.1. Please revise that reference. 11. Sheet A.2; Keynotes: Note 1 references a steel awning and to See Structural. There is no awning information on the structural drawings. Should this be included on Sheet G.1 in Deferred Submittals? Please verify. 12. Sheet A.7; Elevation 3: Please provide the location of the vertical grab bar from the floor per the ICC/ANSI Figure 604.5.1. 13. Sheet S.0; Shop Drawings: Please add a note in the Shop Drawings section to follow the requirements of the IBC Section 107.3.4.1. 14. Sheet S.1; Keynotes: Notes 3 and 18 were not located on the plan. Please verify. 15. Sheet S.2; Roof Framing Plan: At the interior beam line, a Section 3/S.3 is cut. Please revise that Section reference. 16. Sheet S.2; Keynotes: Note 11 references the roof hatch Detail 1/S.4. Please revise that Detail reference. 17. General: Please provide a Special Inspection Certificate with Parts A and B completed. 18. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
12/11/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/11/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | DP must be approved first. Ensure sidewalks adjacent to building are kept flood free from roof drains. |
12/12/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
12/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the civil site utility plan with the plumbing plans. The size of the water service pipe does not match and the building drain is not located close to the building sewer. Reference: Section 107.2.1, IBC 2012. 2. Provide a cleanout in the building sewer prior to entering the right-of-way. Reference: Pima County Standard Detail RWRD 401, 2015. 3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
12/14/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref; 2012 Tucson/Pima County Outdoor Lighting Code. Plan Sheet E.0. The lumen calcs show 4 'E' fixtures and the Site plan and Building plan show 4. Please clarify. 2012 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Plan. |
12/17/2018 | QJONES1 | ZONING | REVIEW | Needs Review | |
12/17/2018 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/17/2018 | QJONES1 | APPROVAL SHELF | Completed |
12/17/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
12/17/2018 | QJONES1 | REJECT SHELF | Completed |