Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM09023
Parcel: 11015231C

Address:
5801 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM09023
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2018 MASHFOR1 FIRE REVIEW Approved
11/26/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Floor Plan: Please provide a north arrow for this plan.
2. Sheet A1; Floor Plan: There are two enlarged plan details marked as 2/A1. Please revise.
3. Sheet A1; Detail 3: Does this detail apply to this project? No expansion joints were located on the plan.
4. Sheet A1; Floor Plan: A note on the floor plan indicates a 4" slab on grade, while Details 3, 4, and 5 on this sheet indicate 5". Please coordinate.
5. Sheet A2; Details 2 and 3: These details indicate a 6" floor slab (see comment 4). Please verify and coordinate the slab thickness.
6. Sheet A2; Foundation Plan: A porch footing indicates Detail 4/A1.1. Please revise the detail sheet.
7. Sheet A3; Elevation 3: Please revise the elevation indicator in the title from 3/A4 to 3/A3.
8. Sheet A4; Sections 2 and 3: These sections indicate an enlarged Detail 11/A7. Please verify (no Detail 11/A7 is indicated on that sheet).
9. Sheet A4; Section 1: A note at an overflow drain references Detail 9/A5. Please revise that reference.
10. Sheet A7.1; Detail 1: Please indicate the base plate size for the column.
11. General: Please provide a Special Inspection Certificate with Parts A and B completed.
12. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
11/26/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/03/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Label the size of the roof drain and roof drain overflow conductors. Reference: Section 1106.2, IPC 2012.
2. Revise the outlet of the rainwater overflow conductor (detail 5/A5). The outlet cover reduces the flow area of the rainwater conductor. Reference: Section 1101.5, IPC 2012.
12/03/2018 ROBERT SHERRY WATER REVIEW Passed
12/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/06/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved
12/07/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM09023 - Mausoleum at Tucson Memorial Park- East Lawn
Building Plan Review (1st Review) Related to DP18-0199
5801 E Grant Road - R-2 Zoning

TRANSMITTAL DATE: December 7, 2018

DUE DATE: December 12, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the Building plans for compliance with the approved development package DP18-0199. While the building plans are consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. Address the following zoning comments and re-submit for plan review.

3. In the R-2 Zone the maximum height allowed is 25 feet. Revise the height note under the Project Information text block of the cover sheet.

4. Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building Plans
12/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please designate a branch circuit # and panel for the receptacles. Provide a panel schedule and location of the panel. Provide conduit, conductor sizes and types.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2019 AVAUGHN1 OUT TO CUSTOMER Completed