Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09010
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2018 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | confirm with the mechanical reviewer (Robert Sherry) that the city of Tucson allows a type II hood for cooking Pizza. |
| 11/21/2018 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please confirm with the mechanical reviewer (Robert Sherry) that the City of Tucson allows a type II hood for cooking pizza. |
| 11/28/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Cover; Project Information: Since there is no indoor seating, this occupancy classification would more nearly follow a retail (M) use. Please verify and adjust occupant loads, plumbing fixture requirements, etc. as required. 2. Cover; Project Information: Please revise the accessibility code from the 2010 ADA to the 2009 ICC/ANSI A117.1. 3. Sheet A-1; Floor Plan: Please verify there is an accessible route to the existing restroom. 4. Sheet A-4; Section 3: Please provide the connection (size and quantity) of the diagonal bracing to the top of the wall and to the structure above. 5. Sheet A-4; Detail 8: Please indicate the spacing of the wall studs. 6. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 12/06/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the size of the existing water meter serving this address. Provide the serial number for the meter and the total water demand the meter serves. Reference: Section 107.2.1, IBC 2012. |
| 12/06/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater (e.g. pizza ovens) will require a gas meter that delivers at least 2-PSIG gas into a regulator located after the meter set. Reference: Section 402.1, IFGC 2012. 2. The hot water capacity with the proposed water heater is only 3.6 GPM with an 100 degree Fahrenheit rise but the hot water demand appears to be approximately 7 GPM using Table E103.3(2) and Table E103.3(3), IPC 2012. Show how the proposed water heater will be able to supply the projected hot water demand. Reference: Section 607.1, IPC 2012. 3. If PEX tubing is used for the water distribution, provide an approved method of disinfection that will not expose the tubing to excessive chlorine levels. Reference: Section 610.1, IPC 2012. 4. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 5. Verify that the vents serving the grease interceptor rise vertically to at least 6" above the flood rims of the interceptor prior to running horizontally. Reference: Section 905.4, IPC 2012. |
| 12/06/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. 2. Provide the installed weight of the rooftop equipment. Reference: Section 302.1, IMC 2012. 3. Condensate drains shall be terminated at an approved disposal location (i.e. not onto the roof). Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. 4. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. 5. Provide a Type I grease hood over the gas-fired conveyor ovens. Reference: Section 507.2.1, IMC 2012. 6. Verify that the proposed Type I hood is equipped to automatically start the hood exhaust fan when cooking operations commence. Reference: Section 507.2.1.1, IMC 2012. 7. Provide structural details to show how the Type I hood will be supported from the building structure in accordance with Section 507.6, IMC 2012. Reference: Section 302.1, IMC 2012. 8. Show that combustible materials (e.g. roof trusses) are not located within 18" of the Type I hood. Reference: Section 507.9, IMC 2012. |
| 12/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1 The quantity of luminaires shown on the Comcheck does nor correlate with the quantity shown on the lighting plan. Please clarify. #2 Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Include the Awning lighting in the lumen calcs. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 1104 for submittal requirements. #3. Ref; Plan Sheet E4. The riser diagram shows panel A as existing and the panel schedule shows it as new. Please clarify. Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/11/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 01/11/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 01/11/2019 | QJONES1 | REJECT SHELF | Completed |