Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM08996
Parcel: 137055330

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08996
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2018 NICHOLAS ROSS ZONING REVIEW Needs Review ZONING REVIEW TRANSMITTAL

FROM: Nick Ross
Lead Planner

PROJECT:
T18CM08996
5373 S. Calle Santa Cruz 101
TI - Renovation

TRANSMITTAL: November 13, 2018

COMMENTS: the following comments are relative to an application for a Special Exception Process (UDC 3.4.2).

This site is located in the C-3 zone (UDC 4.7.22). A non-chartered financial institute is a permitted use in this zone (Table 4.8-4) with a special exception subject to use specific standards 4.9.4.L4.
11/13/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
11/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. Ref; Plan Sheet E200. The mechanical schedule shows an electrical water heater. However it is not included in the electrical floor plan, panel schedule or calcs. Please clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4.
11/13/2018 ROBERT SHERRY WATER REVIEW Completed
11/13/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/13/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Clarify how the drinking fountain will be able to serve bot standing and handicapped users. Reference: Section 410.2, IPC 2012.
11/13/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/30/2018 SVALENZ1 ENGINEERING REVIEW Needs Review
11/30/2018 SVALENZ1 FIRE REVIEW Needs Review