Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T18CM08957
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2018 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T18CM08957 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Update notation on sheet A-8. ELECTRICAL PLANS: 1. Provide a clear working space of 30"wide x 36"deep in front of sub-panel B, E3405.2. This space may not be possible in the HVAC closet with the water heater in the same space. 2. Update the sub-panel B feeder breaker to 100A, or provide a feeder load calculation for determining the minimum size as shown at Table E3704.2(1). 3. Show overcurrent protection not exceeding the allowable conductor ampacity, E3705.5. Show the wire size for feeder circuit #A9/11 with notation or a line diagram. 4. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/11/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 12/11/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 12/11/2018 | QJONES1 | REJECT SHELF | Completed |