Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM08947
Parcel: 13337017F

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM08947
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The basis for the ventilation cooling load calculation is 1500 CFM but the unit specifications show a total of 2760 CFM of outside air. Check the required amount of outside air for the retail sales area using Table 403.3, IMC 2012 and revise the heating/cooling load calculations.