Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The basis for the ventilation cooling load calculation is 1500 CFM but the unit specifications show a total of 2760 CFM of outside air. Check the required amount of outside air for the retail sales area using Table 403.3, IMC 2012 and revise the heating/cooling load calculations.