Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM08947
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The basis for the ventilation cooling load calculation is 1500 CFM but the unit specifications show a total of 2760 CFM of outside air. Check the required amount of outside air for the retail sales area using Table 403.3, IMC 2012 and revise the heating/cooling load calculations. |