Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM08935
Parcel: 133170530

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM08935
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Please enlarge the plans so that the minimum text size is 3/32" (FONT) in size.
#2. Provide electrical plans sealed by an Electrical Engineer registered in the State of Arizona.
#3. Provide a grounding detail for the racking.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2018 QJONES1 APPROVAL SHELF Completed
12/18/2018 QJONES1 OUT TO CUSTOMER Completed
12/18/2018 QJONES1 REJECT SHELF Completed