Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Please enlarge the plans so that the minimum text size is 3/32" (FONT) in size.
#2. Provide electrical plans sealed by an Electrical Engineer registered in the State of Arizona.
#3. Provide a grounding detail for the racking.
#4. The description of the system calls out a 15KW system, yet the inverter is rated at 12KW. Please Clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements.