| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/13/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Please enlarge the plans so that the minimum text size is 3/32" (FONT) in size. #2. Provide electrical plans sealed by an Electrical Engineer registered in the State of Arizona. #3. Provide a grounding detail for the racking. #4. The description of the system calls out a 15KW system, yet the inverter is rated at 12KW. Please Clarify. Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements. |