Permit Number: T18CM08887
Parcel: 140260440

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T18CM08887
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2018 MCASTRO2 ZONING REVIEW Approved
11/07/2018 MCASTRO2 ENGINEERING REVIEW Passed
11/07/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The one line diagram shows a 30 amp circuit breaker feeding panel PC1 and the panel schedule for panel PC shows a 20 amp breaker. Please clarify.
#2. Ref; Plan Sheet E1.
(a) Plan not stamped by a registrant.
(b) The detail showing the panel schedule shows the panel identified as panel A. Please clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC
11/07/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved
11/07/2018 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
11/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the proposed HVAC unit for the new office. Show that the unit complies with the requirements of Section C403, IECC 2012 for capacity, efficiency, and controls.
2. Show how the condensate from the AC unit will be handled.
3. Show how the office will be ventilated
11/08/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/08/2018 MARTIN BROWN FIRE REVIEW Approved
11/08/2018 ROBERT SHERRY WATER REVIEW Completed