Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T18CM08887
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/07/2018 | MCASTRO2 | ZONING | REVIEW | Approved | |
11/07/2018 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
11/07/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The one line diagram shows a 30 amp circuit breaker feeding panel PC1 and the panel schedule for panel PC shows a 20 amp breaker. Please clarify. #2. Ref; Plan Sheet E1. (a) Plan not stamped by a registrant. (b) The detail showing the panel schedule shows the panel identified as panel A. Please clarify. Ref; 2012 IBC sec 107.2.1, 2011 NEC |
11/07/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/07/2018 | ANY | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active | |
11/08/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specifications for the proposed HVAC unit for the new office. Show that the unit complies with the requirements of Section C403, IECC 2012 for capacity, efficiency, and controls. 2. Show how the condensate from the AC unit will be handled. 3. Show how the office will be ventilated |
11/08/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
11/08/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/08/2018 | ROBERT SHERRY | WATER | REVIEW | Completed |