Permit Number: T18CM08866
Parcel: 12310001H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM08866
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/29/2019 DAVID RIVERA ZONING REVIEW Approved
01/29/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; plan Sheet E1.4.4. The feeders in the clouded in area are not marked or identified for sizes.
Ref; 2012 IBC sec 107.2.1, 2011 NEC