Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM08866
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/29/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/29/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; plan Sheet E1.4.4. The feeders in the clouded in area are not marked or identified for sizes. Ref; 2012 IBC sec 107.2.1, 2011 NEC |