Permit Number: T18CM08866
Parcel: 12310001H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08866
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2018 MARTIN BROWN FIRE REVIEW Approved
11/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G4.3.1: A note in the title block indicates "PROGRESS PRINT FOR PRICING ONLY". Please remove that note.
2. Sheet A9.5.1; Details 3, 6, and 9: A note on these details indicates "Ceiling Detail: 1. Typical (3XX): See 4/A9.5.3". Please verify this note is correct.
3. Sheet A9.5.1; Detail 5: This detail does not indicate any delta change, although the narrative indicates a change. Please verify.
4. General: Please provide written responses to all review comments.
11/28/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/28/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/28/2018 ROBERT SHERRY WATER REVIEW Completed
12/03/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E1.4.3. The feeder schedule does not correlate with the line diagram for the proposed new panels and feeder from the bus.
#2. Ref; Plan Sheet E1.4.4.
(a) Provide a feeder schedule that correlates with the bus and panel or equipment schedules.
(b) Panel 4CAAL2 is shown with bold print. Is this part of the scope of work?
#3. Ref; Plan Sheets E1.4.3 and E1.4.4. Update the load calcs for the increase in loads to the equipment upstream of the new panels or equipment.
#4. Ref; Plan Sheet E4.9.6. Could not locate Plan Sheets E8.0.6 and E8.0.2, associated with Details 3 and 4.
#5. Ref; Plan Sheet E4.9.7. Could not locate Plan Sheets E8.0.1 and E8.0.6, associated with details 3 and 4.
#6. Ref; Plan Sheet E5.9.7. Please be more specific as to the scope of work proposed in the clouded areas.
#7. Plan Sheets E8.0.1, E8.0.2, E8.0.6, E83.2 were not included with this submittal.
#8. Provide a symbol and legend Plan in order to define the abbreviations and symbols.
#9. Provide a spec sheet for the prescribed wiring methods, devices, and a note that requires the proposed electrical installations to comply with NEC art 517.
#10. Provide a complete luminaire schedule.
#11. A complete electrical plan review could not be completed at this time due to insufficient information provided with the submittal. Be advised that additional plan review comments may be generated at the subsequent review.

Ref; 2012 IBC sec 107.2.1, 2011 NEC.
12/05/2018 QJONES1 ENGINEERING REVIEW Passed
12/05/2018 QJONES1 ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM08866 - Banner University Medical Center Tucson Expansion and Renovation
Building plans (Revisions #8 review)
1501 N Campbell Avenue

TRANSMITTAL DATE: December 5, 2018

DUE DATE: December 6, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. The proposed revisions to the interior do not affect any zoning requirements and the use of the building and site is not changing.


2. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and no site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2018 QJONES1 APPROVAL SHELF Completed
12/07/2018 QJONES1 OUT TO CUSTOMER Completed
12/07/2018 QJONES1 REJECT SHELF Completed