Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T18CM08835
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 1; Sheet TS1; Code Study: Please provide calculations on this sheet for the required plumbing fixtures in Building A. At this time, no indication of required fixtures is presented. 2. Previous Comment 2; Sheet ASP1; Exiting Plans: Please indicate on this sheet the total occupant load for Building A. 3. Previous Comment 6; Sheet A2.2; Second Floor Reflected Ceiling Plan: No exit lighting was indicated on these plans. Please provide. 4. Sheet A2.2; Second Floor Reflected Ceiling Plan: The reflected ceiling plan for the revised open area (as indicated on Sheet A2.1) should be indicated on Sheet A2.2. Please verify. 5. Sheet A3.0; Detail 7: A reference in this detail is made to Section 217/S5.0 for the steel post attachment to the masonry wall. Please revise that reference. 6. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 04/19/2019 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/25/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/25/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The submitted cut-sheets for the shampoo sink do not indicate that it is a listed product. The sink will have to be third party listed or an engineer will have to show that the unit meets all applicable standards as an alternative material or equipment. Reference: Section 105.2, IPC 2012. [Initial comment: Revise the plumbing fixture schedule to require a third party listing for the shampoo sinks (P7) supplied by the owner. Reference: Section 303.4, IPC 2012.] |
| 04/26/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/03/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |