Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM08835
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/23/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS1; Code Study: Please provide calculations on this sheet for the required plumbing fixtures in Building A per the IBC Table 2902.1. 2. Sheet ASP1; First and Second Floor Exiting Plans: Please indicate on this sheet the total occupant load for each floor in Building A. 3. Sheet A0.1; Standard Dwelling Toilet Stall: Please provide a detail on this sheet for the back wall grab bar per the ICC/ANSI Figure 604.5.2. 4. Sheet A1.1; First Floor Plan: An exterior wall in Rooms 104 and 109 indicates wall type EM. Should these be wall types EF4? Please verify. 5. Sheets A1.1 and A1.2; Partition Types: For all rated wall assemblies, please indicate the U.L. Listing Number on this sheet. 6. Sheets A2.1 and A2.2; Reflected Ceiling Plan: Please indicate the exit lighting on these plans, or reference the electrical Sheets E3.1 and E3.2. 7. Sheet S4.0; Detail 105: A note indicates to see Detail 213 for the lintel steel bent plate. Please revise that note. 8. General: Please provide a Special Inspection Certificate with Parts A and B completed. 9. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucson az.gov |
| 11/28/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Keynotes 20 and 21 on sheet P1.1 note water service for two buildings not located on the same parcel of land. The two other buildings have their own functioning water meters while the 2" water meter indicated on sheet P1.1 has not had any flow for some time. Verify any water connections to the two other buildings. |
| 11/28/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The Rheem model HE119-199 water heater has a storage volume of 119-gallons. Lined water heaters with a nominal water containing capacity of 120 gallons or more are required to comply with the rules contained in Article 4 (Arizona Boilers and Lined Hot Water Heaters) of the Arizona Administrative Code. https://www.azsos.gov/rules/arizona-administrative-code#ID20. 2. Revise the configuration of the natural gas sediment trap, as shown in detail 1/P3.1 to comply with the requirements of Section 408.4, IFGC 2012 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible). 3. Revise the plumbing fixture schedule to require a third-party listing for the shampoo sinks (P7) supplied by the owner. Reference: Section 303.4, IPC 2012. 4. Verify that horizontal branches connect no closer than ten diameters downstream of the bases of vertical stacks. See Riser diagrams 1/P2.2, 1/P2.3, 3/P2.3, 1/P2.4 and 3/P2.4. Reference: Section 704.3, IPC 2012. |
| 11/29/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012. 2. Provide heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. |
| 12/05/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM08834 and T18CM08835 - Commercial Uses Administrative Office / Personal Services - Salon Building plans (1st Review) 2010 N Camino Serna and 2030 N Camino Serna TRANSMITTAL DATE: January 17, 2018 DUE DATE: January 18, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. The proposed modifications to the interior do not affect any zoning requirements. Exterior Modifications: For the 2010 building, a new elevator (SF Minimal) is proposed and 2 new ADA parking spaces with accessible ramp along the south side of the building. For building 2030, relocation of one of existing ADA spaces next to another existing ADA space along the north side of building. While the exterior modifications are minimal a DP is required because of these changes. Sheet ASP1 can be used as the DP for purposes of the DP requirement. The DP stamp can be downloaded from the PDSD web site or PDSD staff can apply the ink stamp on the next submittal. 2. COMMENT: On sheet ASP1 which can be used for the DP, the parking requirements for the Salons shall be revised to state the requirement is 1 space per 300 SF. It is acknowledged that there is excess parking overall, but the correct ration should be used. 3. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and the DP is approved and no additional site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 12/06/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Please identify all the electrical panels on the electrical floor plans. Ref; 2012 IBC 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/10/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 04/10/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 04/10/2019 | QJONES1 | REJECT SHELF | Completed |