Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM08834
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS1; Code Study (Area); Code Analysis (General Building Summary): The Code Study Area indicates 10,263 SF for Building B, while the Code Analysis General Building Summary indicates 10,218 SF. Please coordinate. 2. Sheet TS1; Code Study: Please provide calculations on this sheet for the required plumbing fixtures in Building B. Verify the existing restroom count is adequate for the stated occupant load. 3. Previous Comment 1; Sheet ASP1; Exiting Plans: Please indicate on this sheet the total occupant load for Building B first floor, second floor, and building total. 4. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 04/19/2019 | STEVE SHIELDS | ZONING | REVIEW | Approved |