Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1; Code Study (Area); Code Analysis (General Building Summary): The Code Study Area indicates 10,263 SF for Building B, while the Code Analysis General Building Summary indicates 10,218 SF. Please coordinate.
2. Sheet TS1; Code Study: Please provide calculations on this sheet for the required plumbing fixtures in Building B. Verify the existing restroom count is adequate for the stated occupant load.
3. Previous Comment 1; Sheet ASP1; Exiting Plans: Please indicate on this sheet the total occupant load for Building B first floor, second floor, and building total.
4. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
04/19/2019 STEVE SHIELDS ZONING REVIEW Approved