Permit Number: T18CM08834
Parcel: 13316039A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08834
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2018 MARTIN BROWN FIRE REVIEW Approved
11/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet ASP1; Exiting Plans: If a new certificate of occupancy is required tor Building B, please provide on this sheet the total occupant load for each floor.
2. Sheets A1.1 and A1.2; Partition Types: For all rated wall assemblies, please indicate on these sheets the U.L.Listing number.
3. Sheet A3.0; Roof Plan: At the new elevator, an enlarged plan indicator references 3/A3.0. Please revise that reference.
4. Sheet A7.0; Enlarged Plan 1: For the rated wall assemblies, please indicate on these sheets the U.L.Listing number.
5. Sheet S2.0 (Foundation Plan); Structural Calculations: Please provide structural calculations for the elevator shear wall and footing designs.
6. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
11/28/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/28/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/28/2018 ROBERT SHERRY WATER REVIEW Completed
12/05/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM08834 and T18CM08835 - Commercial Uses
Administrative Office / Personal Services - Salon
Building plans (1st Review)
2010 N Camino Serna and 2030 N Camino Serna

TRANSMITTAL DATE: January 17, 2018

DUE DATE: January 18, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. The proposed modifications to the interior do not affect any zoning requirements.

Exterior Modifications: For the 2010 building, a new elevator (SF Minimal) is proposed and 2 new ADA parking spaces with accessible ramp along the south side of the building. For building 2030, relocation of one of existing ADA spaces next to another existing ADA space along the north side of building.

While the exterior modifications are minimal a DP is required because of these changes. Sheet ASP1 can be used as the DP for purposes of the DP requirement. The DP stamp can be downloaded from the PDSD web site or PDSD staff can apply the ink stamp on the next submittal.

2. COMMENT: On sheet ASP1 which can be used for the DP, the parking requirements for the Salons shall be revised to state the requirement is 1 space per 300 SF. It is acknowledged that there is excess parking overall, but the correct ration should be used.

3. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and the DP is approved and no additional site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
12/06/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2019 QJONES1 APPROVAL SHELF Completed
04/04/2019 QJONES1 OUT TO CUSTOMER Completed
04/04/2019 QJONES1 REJECT SHELF Completed