Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM08827
Parcel: 12212010B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08827
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets A0.0 and CS; Design Codes: Please replace the 2010 ADA Standards for Accessible Design with the 2009 ICC/ANSI A117.1 Accessibility Code.
2. Sheet A0.0; Deferred Submittals: Please reference the IBC Section 107.3.4.1 in these notes on Sheet A0.0.
3. Sheet CS; Egress Floor Plan: Per the IBC Section 1016.3, the exit access travel distance shall be measured along horizontal and vertical paths. Please revise the Egress Plan, removing all diagonal paths of egress.
4. Sheet CS; Toilet Rooms #1 and #2; Typical Mounting Heights: The Toilet Room Plan indicates the length of the side wall grab bar as 4'-0", while the Mounting Height indicates 3'-6". Please clarify.
5. Sheet CS; Toilet Rooms #1 and #2: Please indicate the vertical grab bar on the plans per the Mounting Heights details.
6. Sheet CS; Egress Floor Plan: Per the IBC Table 1021.2(2), for a B Occupancy with one exit, the maximum exit access travel distance is 100 feet (for sprinklered space). Please indicate on the plan that requirement is met.
7. Sheet D1.0; Demolition Plan Key Notes: Please add a note to Key Note 11 to reference Detail 2 for the slab infill.
8. Sheet A1.1; Elevation 4: At the bottom of the stair, a dimension at the handrail indicates 3'-6" to an intermediate rail. Please verify this dimension at that location.
9. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
11/19/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations for the three proposed rooftop AC units, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.
2. Show that the proposed HVAC control system for the three rooftop units will provide for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the system is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if manual changeover from the heating and cooling modes is not required, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
3. Condensate drains shall be terminated at an approved disposal location. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
4. The ventilation calculations identify ten areas as "pet shop" but only provide exhaust for two of the areas. If these areas are not best describe a pet areas, revise the calculations as needed (e.g. the operating room might be described as having an occupant density of 10 people per 1,000 square feet and needing 25 CFM per person). Reference: Section 403.3, IMC 2012.
11/19/2018 MARTIN BROWN FIRE REVIEW Approved Address on cover sheet incorrect
11/20/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a complete diagram of the modified natural gas distribution system, showing the all of the loads, developed lengths, and the pipe sizes. Reference: Section 107.2.1, IBC 2012 and Sections 402.1 and 402.3, IFGC 2012.
2. Revise the configuration of the natural gas sediment trap, as shown in detail 9/P5.1, to comply with the requirements of Section 408.4, IFGC 2012 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible).
3. Revise the design criteria of the water distribution system to provide a flow pressure of 15 PSI or the flow pressure prescribed by the fixture or appliance manufacturer, whichever is greater. Reference: Section 604.3, IPC 2012, as amended by the City of Tucson.
4. Provide information to show that the installation of the thermal expansion tank complies with the manufacturer's listing requirements (i.e. on the cold water supply line, between the water heater and the shut off valve or check valve). Reference: Sections 303.2 and 607.3.2, IPC 2012.
5. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
6. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
7. Verify that hot water with a minimum temperature of 110 degrees Fahrenheit is delivered to the mop sink for building maintenance purposes. Reference: Section 607.1, IPC 2012.
11/20/2018 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the serial number of the water meter serving this suite and the total demand it will see. Note: Tucson Water does not allow water meters to be manifolded to increase capacity. Reference: Section 107.2.1, IBC 2012.
2. Provide the size and indicate the location of the reduced pressure principle backflow prevention assembly associated with the water meter.
3. Verify the water pressure range for this address. The area in question normally runs in excess of 80 PSI. Contact Tucson Water for assistance (Ray Munoz, 520-837-2207).
11/29/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E5.1.
(a) Indicate conduit, conductor sizes and types between the service disconnects and the pull box.
(b) Indicate the location of the main service on the plans. If located remote of the New panels M1 and M2, indicate the wiring methods utilized for the installation of the feeders from the service to the panel locations.
(c) Keyed note #1. It is the responsibility of the Engineer of record to calculate fault currents. Not the contractor. R4-30-302. Electrical Plans. A registrant shall prepare and submit drawings and specifications for a new electrical system or an addition or modification to an existing electrical system provided the service and associated electrical feeders exceeds 600 amperes 120/240 volts, single phase or 225 amperes 120/208 volts, three phase and the fault current exceeds 10,000 amperes.
(d) Could not locate Keyed Note #2 shown at the service meters.
(e) Indicate what the external grounds are for that are terminated at the service disconnects for panel M1 and M2.
(f) Both of the panels are labeled M1. Please Clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC
12/05/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
12/05/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Banfield Pet Hospital - Animal Service
T18CM08827 (1st Review)
4615 E Speedway C-2 Zoning (Within a Shopping Center Development)

TRANSMITTAL DATE: December 5, 2018

DUE DATE: December 5, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has reviewed the T. I. but cannot approve the plans on this review. Address all reviewers' comments and resubmit.

02. COMMENT: Correct the site address on the cover sheet to 4615 E. Speedway Boulevard.

03. COMMENT: List the following as a general note on the cover sheet:

Proposed Use: Animal Service - Pet Hospital Subject to UDC Sections; C-2: 4.9.4.D.1, .2, .3, & .4 and 4.9.13.P

4.9.4. D. Animal Service
1. Overnight confinement for clinic treatment is permitted for a maximum of five animals .
2. Boarding of animals is prohibited.
3. The activity shall be within a completely enclosed building.
4. An outpatient clinic is permitted for small animals only.
4.9.13.P. C-2 Commercial Zone - General Restrictions
1. Outdoor display of finished products for rent or sale at retail or wholesale is permitted, unless prohibited by a use-specific standard.
2. The land uses in the Commercial Services (except Automotive Service and Repair, Day Care Use; Medical Service, Extended Health Care; Transportation Services, Land Carrier; and Travelers' Accommodation, Lodging) Industrial, Restricted Adult Activities, and Wholesaling Use Groups shall be conducted entirely within an enclosed building unless modified by Use Specific Standards.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans