Permit Number: T18CM08803
Parcel: 12701001B

Address:
421 N ARCADIA AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM08803
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2018 MARTIN BROWN FIRE REVIEW Approved
11/14/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change Plan review by: Gilbert Peru
p: 520-837-6962
Gilbert.Peru@tucsonaz.gov

1. The structural adequacy of the existing monopole for support of the new imposed loads must be determined and verified with the submittal of structural calculations and analysis. IBC 1603.1.

Please provide written responses to plan review comments.
11/14/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review by: Gilbert Peru
p: 520-837-6962
Gilbert.Peru@tucsonaz.gov

1. Please submit grounding details for all new equipment. NEC 250.4

Please provide written responses to plan review comments.
11/20/2018 SMONTES1 PLANNING-CITY HALL REVIEW Passed
12/03/2018 QJONES1 COMMUNICATIONS REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2018 QJONES1 APPROVAL SHELF Completed
12/03/2018 QJONES1 OUT TO CUSTOMER Completed
12/03/2018 QJONES1 REJECT SHELF Completed