Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Indicate the wiring methods utilized for the terminations in the wireway.
#2. Indicate conduit, conductor sizes and types for all the feeders between the CT cabinet to the disconnect switches.
#3. Indicate fuse sizes and types in the service disconnect switches.
#4. Provide for a complete grounding electrode system including Water, Gas, Building Steel and grounding of both electrical services to be common per NEC art 250.58
Ref; 2012 IBC sec 107.2.1, 2011 NEC