Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM08715
Parcel: 13704135F

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM08715
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Indicate the wiring methods utilized for the terminations in the wireway.
#2. Indicate conduit, conductor sizes and types for all the feeders between the CT cabinet to the disconnect switches.
#3. Indicate fuse sizes and types in the service disconnect switches.
#4. Provide for a complete grounding electrode system including Water, Gas, Building Steel and grounding of both electrical services to be common per NEC art 250.58
Ref; 2012 IBC sec 107.2.1, 2011 NEC