Permit Number: T18CM08713
Parcel: 11005014C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08713
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide dimensions to the office tenant remodel; show lengths of exterior walls. IBC 107.2.1
2. Please provide dimensions for the common path of egress travel inside the tenant space measured 1 ft. from the wall line because there is no information on office layout. IBC 1014.3
4. Identify all architectural features in the tenant space; elevator, exit doors. IBC 107.2.1
5. Identify the exit doors from the tenant space; show EXIT sign at exit door.
6. Specify type and source of means of egress illumination. IBC 1006.1.
7.
10/31/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/31/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/31/2018 ROBERT SHERRY WATER REVIEW Completed
10/31/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/13/2018 SVALENZ1 ENGINEERING REVIEW Needs Review
11/13/2018 SVALENZ1 ZONING REVIEW Needs Review
11/13/2018 SVALENZ1 FIRE REVIEW Needs Review
11/13/2018 SVALENZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed GP PASSED IT