Permit Number: T18CM08622
Parcel: 130130580

Address:
3775 E 34TH ST

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T18CM08622
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/03/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an analysis of the occupancy classification for the infusion kitchen. Include a listing of the materials to be stored and used in the space, their hazard ratings and quantities in use or stored. Reference: Sections 107.2.1 and 302.1, IBC 2018.
2. Provide a description of the processes that will be performed under the proposed hood and in the proposed oven. Reference: Sections 501.3, 502.1, 502.8, and 502.9.5, IMC 2018.
3. Provide a complete mechanical plan for the installation of the process hood and the process oven. Reference: Section 107.2.1, IBC 2018.
4. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2021 PCAMARE1 OUT TO CUSTOMER Completed