Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM08596
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. When the clothes washer is not near an exterior wall show a bathing fixture drain looped 3' beyond an exterior wall below grade before connection to the building drain. See details at https://www.tucsonaz.gov/files/pdsd/codes-ordinances/Grey_Water_Options_FINAL_.pdf

FOUNDATION PLANS:

1. Show interior braced wall panels with foundation anchor bolt connection to bottom plates, R602.10.8.3 and R403.1.6.

FLOOR PLANS:

1. Locate and identify brace wall lines on the plans, R602.10.1 along with appropriate panel lengths, R602.10.3 for an identified method, R602.10.4 and connection schedule, Table R602.10.4.

STRUCTURAL PLANS:

1. Identify each wall line needed for enclosing a complete rectangle with sides no greater than 60', Figure R602.10.1.1. Place these lines no further than 4' from an actual parallel wall, so that corners are no further than 10' from a "qualifying" braced wall panel, or provide an engineer's calculation, design and seal for shear wall placement.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air or continuous exhaust fan function.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal. The deferred calculations must be approved through revision process prior to mechanical inspections.
3. Show combustion air compliance for appliances in confined spaces, G2407.5.3.1.
4. Show ignition source appliances installed in (or accessed from) garages with platforms at least 18" above the floor, M1307.3, G2408.2 & P2801.6.

ELECTRICAL PLANS:

1. Show the dishwasher/disposal on circuit #23 with 20A breaker, E3703.7.
2. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review