Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM08440
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/05/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S6 (Detail 101); Structural Calculations (Page 1): The calculations indicate the purlins are 8" x 3.5" x 14 ga., while the drawing indicates a 9" x 3" x 14 ga. Please clarify. |
| 11/07/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheets E1.2. E1.5. What is the rectangular boxes with E1.3B and E1.5A at the AC DISCONNECT SWITCH supposed to represent? #2. Indicate the types and sizes of the fuses in the AC DISCONNECT. #3. Ref; Plan Sheet E3.3, Detail 4. The grounding conductor should be bonded to the conduit, not the grounded conductor. NEC 250. #4. Ref; Plan Sheet EL 1.1. Provide a grounding and bonding detail for the transformers utilized for the under canopy lighting. NEC 250.30. Ref; 2012 IBC sec 107.2.1, 2011 NEC. |
| 11/08/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 11/13/2018 | DAVID RIVERA | ZONING | REVIEW | Approved |