Permit Number: T18CM08440
Parcel: 12907006V

Address:
1575 E 36TH ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM08440
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2018 MARTIN BROWN FIRE REVIEW Approved
11/05/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S6 (Detail 101); Structural Calculations (Page 1): The calculations indicate the purlins are 8" x 3.5" x 14 ga., while the drawing indicates a 9" x 3" x 14 ga. Please clarify.
11/07/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheets E1.2. E1.5. What is the rectangular boxes with E1.3B and E1.5A at the AC DISCONNECT SWITCH supposed to represent?
#2. Indicate the types and sizes of the fuses in the AC DISCONNECT.
#3. Ref; Plan Sheet E3.3, Detail 4. The grounding conductor should be bonded to the conduit, not the grounded conductor. NEC 250.
#4. Ref; Plan Sheet EL 1.1. Provide a grounding and bonding detail for the transformers utilized for the under canopy lighting. NEC 250.30.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.
11/08/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
11/13/2018 DAVID RIVERA ZONING REVIEW Approved