Permit Number: T18CM08414
Parcel: 110120910

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08414
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2018 EHAMBLI1 ZONING REVIEW Approved
10/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Designate a branch circuit and panel for the lighting, power, exhaust fan.
#2. Clearly indicate the scope of work for the power and lighting, fire alarm system.
#3. Provide a power and lighting demolition plan.
#4. Show all new electrical or lighting installed in the new or relocated wall or partitions.
#5. Provide complete exterior lumen calcs as required per section 104 of the Tucson/Pima County Outdoor Lighting Code.. Parcel size in acres, total allowed lumens per sec 401.1.
#6. Show the locations on the floor plans of the panelboards associated with the proposed work. Also complete panel schedules.
Ref; 2012 IBC 107.2.1, 2011 NEC 408.4, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd.
10/22/2018 EHAMBLI1 ENGINEERING REVIEW Passed
10/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/22/2018 ROBERT SHERRY WATER REVIEW Completed
10/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/22/2018 JVINCEN1 FIRE REVIEW Approved
10/22/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed