Permit Number: T18CM08366
Parcel: 117170010

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08366
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify the new bar area has adequate ventilation per Section 403.3, IMC 2012.
10/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/22/2018 MASHFOR1 FIRE REVIEW Approved
10/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. a 3.0 Revise the door swing at the main entrance to swing in the direction of egress travel due to the occupant load over 50 persons.
2. Specify panic or exit hardware on the esit doors.
3. Show the location of the EXIT signage.
4. If new walls or partitions are being constructed need to provide frame details that show wall stud and wall covering and connection of new walls to the roof/ceiling and floor.
5. The ratio for water closets for male and female for a bar occupancy is 1 per 40, not 1 per 75. IBC TABLE 2902.1
10/22/2018 ROBERT SHERRY WATER REVIEW Completed
10/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
10/24/2018 EHAMBLI1 ENGINEERING REVIEW Passed
10/24/2018 EHAMBLI1 ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2018 QJONES1 APPROVAL SHELF Completed
10/24/2018 QJONES1 OUT TO CUSTOMER Completed
10/24/2018 QJONES1 REJECT SHELF Completed