Permit Number: T18CM08350
Parcel: 135104610

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM08350
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2019 AVAUGHN1 ENGINEERING REVIEW Completed
10/19/2018 KELLY LEE ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Kelly Lee, Lead Planner
PDSD Zoning Review Section

PROJECT: 7245 E Golf Links
T18CM08350

TRANSMITTAL DATE: October 19, 2018

1. Provide clarification on keynote 17 on sheet1. Where is the 8-foot vinyl fence on the plan?

2. New ADA paint symbols are shown on sheet 1 for parking along south property line. New ADA signage is required.
10/19/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Please provide complete electrical power and lighting plans. The design for power and lighting and designation for branch circuits are not to be performed by the contractor.
#2. Provide complete panel schedules.
#3. Provide a complete luminaire schedule.
#4. Provide complete compliance with the 2012 IECC for the lighting.
#5. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting on the parcel. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4, City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd.
10/19/2018 ROBERT SHERRY WATER REVIEW Completed
10/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/19/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/19/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/23/2018 MASHFOR1 FIRE REVIEW Approved Operational Permit will need to be obtained from TFD for "Places of Assembly Permit"

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2019 AVAUGHN1 OUT TO CUSTOMER Completed
04/30/2019 AVAUGHN1 REJECT SHELF Completed