| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet E4. (a) Keynote 4 states to provide a 100 amp 3 pole circuit breaker for panel X. This 100 amp breaker is not shown in the panel schedule for panel X. Please clarify. (b) Identify the new 75 KVA transformer and indicate the type of grounding electrode utilized. If the grounding electrode is not one of the types as specified in NEC art 250.66 A through C, the grounding electrode conductor will need to a #2 AWG Copper per table 250.66. #2. Provide for an OCPD at or ahead of New Panel C as specified per NEC art 408.36B. #3. Ref; Plan Sheet E4 and E5. Key Note 2 (E4) states to "PROVIDE 225 AMP PANEL WITH 225 AMP MAIN BREAKER". However, the panel schedule shows a 200 AMP panel with 200 AMP bus, Main Lug Only. Please clarify. Ref; 2012 IBC sec 107.2.1, 2011 NEC |