Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T18CM08181
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/14/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Comment not resolved; provide the size of the backflow preventer associated with the water meter, and the estimated total water demand to be served by the water meter. [Initial comment: Insufficient information to evaluate. Provide the size of the proposed water meter to serve this building, the size of the backflow preventer associated with the water meter, and the estimated total water demand to be served by the water meter. Reference: Section 107.2.1, IBC 2012.] 2. NOTE: sheet MP1.0 has not been sealed and the north arrow of the plumbing plan points to the south. |
11/15/2018 | SVALENZ1 | ZONING | REVIEW | Needs Review | |
11/15/2018 | SVALENZ1 | ENGINEERING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/15/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |