Permit Number: T18CM08181
Parcel: 12004002B

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T18CM08181
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2018 MARTIN BROWN FIRE REVIEW Approved Deferred submittal for Fire Sprinkler/Alarm, and undground will supplied to Fire per the plans
11/06/2018 ROBERT SHERRY WATER REVIEW Reqs Change Insufficient information to evaluate. Provide the size of the proposed water meter to serve this building, the size of the backflow preventer associated with the water meter, and the estimated total water demand to be served by the water meter. Reference: Section 107.2.1, IBC 2012.
11/08/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM08181

1) Building site plan shown does not match site plan in DP16-0044 (Approved on 10/30/2018). Provide an updated building site plan that corresponds to the most recently approved DP
a. Parking layout
b. Sidewalk width around building
2) Coordinate with Development Package (DP) to ensure that roof drains scupper underneath sidewalks. Reference City of Tucson Technical Standards Manual (TSM) section 7-01.4.1.E
3) Once the above and any outstanding commercial review comments have been addressed, Engineering can conduct an over the counter review of the building plans. Call or Email to Schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
11/08/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM08181 - New Building (Retail Use - General Merchandise)
Building Plan Review (1st Review) The Landing, Lot 11 - Shell Building
4790 S. Calle Santa Cruz - Zoning PAD 29, Related to DP16-0044


TRANSMITTAL DATE: November 8, 2018

DUE DATE: November 9, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package revision 6. While the building footprint and the site revisions are somewhat consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the 3rd Party and PDSD Commercial Plans reviewers have approved the building plans.

Prior to approval of the building plans the DP must be revised to match what is proposed on the building plans or vice versa. The site plan in the building package does not match the approved site plan on the DP. Per the building plans, there are pop outs along the exterior walls of the building that encroach onto the pedestrian sidewalks. The site plan in the DP does not depict the pop outs. The sidewalks are dimensioned to specific widths on the DP sidewalk but do not match the site plan in the building package.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. (Include a copy of the approved and PDSD stamped version of the DP with the next building submittal.)

If the DP is revised to match the building package site plan assure that the footprint, sidewalks, ADA crosswalks, any differences between the DP site plan and building plan site plan are consistent.

3. COMMENT: If any changes are necessary, due to the 3rd Party or PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning.

It appears that either the DP or building plans will have to be revised for consistency.

4. COMMENT: Once the plans have been reviewed and approved by the 3rd Party and PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building plans and revised DP
11/13/2018 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/13/2018 QJONES1 APPROVAL SHELF Completed
11/13/2018 QJONES1 OUT TO CUSTOMER Completed
11/13/2018 QJONES1 REJECT SHELF Completed