Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM08172
Parcel: 11811007B

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T18CM08172
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Specify length time of the automatic time-out for the specified sensor faucet for the L-2 lavatories so that it will dispense a maximum of 0.25 gallons per metering cycle. (Alternatively, specify the maximum volume of water to be dispensed per cycle as was done for lavatory L-1 faucets.) Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
03/20/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide compliance with section 403.5 Outdoor lighting Code for the unshielded exterior lighting. (Curfew Requirements).
Ref; 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2019 AMARTIN1 OUT TO CUSTOMER Completed