Permit Number: T18CM08149
Parcel: 14101006C

Address:
9900 E DREXEL RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM08149
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 86 of 120; Specifications (13 34 23-2 through 23-8): The specifications indicate the ramadas require shop drawings that include the manufacturer's standard details and structural calculations, the manufacturer's literature and technical data, and drawings, details, and calculations sealed and signed by a structural engineer licensed in the state of Arizona. Please reference the specifications for all requirements. All submittals must meet the requirements of the 2012 IBC Section 107.3.4.1.
2. Sheet 88 of 120: Are there structural calculations for the concrete walls, footings, and stair design? Please provide.
3. Sheet 89 of 120: Are there structural calculations for the concrete walls, footings, and hanging baffle design? Please provide.
4. Sheet A2.3 (Staff Restroom); Mounting Heights Schedule: Please indicate the location of the side grab bar from the rear wall per the ICC/ANSI Figure 604.5.1.
5. Sheet A2.3 (Staff Restroom); Interior Elevations: Please indicate the location of the rear wall horizontal grab bar per the ICC/ANSI Figure 604.5.2.
6. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
11/13/2018 ROBERT SHERRY WATER REVIEW Passed
11/13/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/13/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the location of the check valves and full-open valves for the sump pumps, P171A and P171B, are accessible per Section 712.2, IPC 2012.
11/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/21/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM08149 - SE Houghton Area Recharge Project
Building plans (1st Review)
9900 E. Drexel Road

TRANSMITTAL DATE: November 21, 2018

DUE DATE: November 27, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the current unapproved version of the development package. While the building footprint is consistent with the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until DP is approved.


2. COMMENT: In addition, the building plans must be approved by the PDSD commercial plans reviewers before zoning can approve the plans.


3. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and no site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview.


4. COMMENT: Remove the remove the unapproved sheets in the building package that are stamped with the PDSD approval stamp or mark them as reference or prior to final approval of the building plans include copies of the approved, stamped and signed DP sheets in the building plan package.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
11/29/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM08149

1) Once the development plan has been approved and any outstanding department review comments have been addressed, Engineering can conduct an over the counter review and approval of the building plans. Call or email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007

Final Status

Task End Date Reviewer's Name Type of Review Description
05/09/2019 PMARTIN1 OUT TO CUSTOMER Completed