Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM08145
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/11/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/11/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. There is only one junction of the building drain and the building sewer in this warehouse shell but sheet P1.1 shows three 2-way cleanouts. See the definitions for building drain and building sewer in Section 202, IPC 2012. [Initial comment: An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.5 and 708.5, IPC 2012.] 2. The water pipe schedule on the new sheet P2.1 allows the use of PEX piping for this activity. Provide instructions for disinfecting PEX pipe that are acceptable to the manufacturer of the material and comparable to the disinfection method described in Section 610.1, IPC 2012. Reference: Section 302.2, IPC 2012. |
| 01/14/2019 | QJONES1 | ZONING | REVIEW | Needs Review | |
| 01/14/2019 | QJONES1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/14/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 01/14/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 01/14/2019 | QJONES1 | REJECT SHELF | Completed |