Permit Number: T18CM08140
Parcel: 14043011A

Address:
7211 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM08140
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Structural calculations are required for this project. IBC 107.2.1.
11/15/2018 MASHFOR1 FIRE REVIEW Approved Deferred Submittal is required to be supplied to TFD regardless of FP1 page for Fire Sprinklers
11/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E1.0.
(a) Clarify GENERAL NOTE 'C'. What Code are those references from?
(b) Show how the luminaires are controlled.
#2.Ref; Plan Sheet E2.0.
(a) Where are the sample photos as stated in KEYED NOTE #2?
(b) Provide more detail in the branch circuit description for the lighting and receptacles (location) in the panel schedule. NEC 408.4.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2018 AVAUGHN1 OUT TO CUSTOMER Completed