Permit Number: T18CM08099
Parcel: 13101053B

Address:
1255 S SWAN RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM08099
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Per the IBC Section 107.3.4.1, deferred submittals shall be submitted to the registered design professional in responsible charge who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and found to be in general conformance to the design of the building. Deferred submittal items shall not be installed until those documents have been approved by the Building Official. Please follow this requirement.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2019 QJONES1 APPROVAL SHELF Completed
05/10/2019 QJONES1 OUT TO CUSTOMER Completed
05/10/2019 QJONES1 REJECT SHELF Completed