Permit Number: T18CM08096
Parcel: 117032030

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T18CM08096
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T18CM08096
231 W. University Blvd.
Residential (1st Review)

TRANSMITTAL DATE: October 25, 2018

The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-3 zone (UDC 4.7.12). A multi-family residence is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6

1. A Design Development Option (DDO) for setbacks and Historic Preservation Zone (HPZ) for demolition, must be approved prior to Zoning approving the building plans. Both the DDO and HPZ section will need to stamp and approve the plans prior to Zoning approval.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/30/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM08096
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1.

FLOOR PLANS:

1. Show under-floor space ventilation openings with not less than 1 SF for each 150 SF of under-floor area, R408.2.

SECTIONS - DETAILS:

1. Calculate and show the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Update sheet a4.

ELECTRICAL PLANS:

1. Clarify the location of keynote #1 on the plan, R106.1.1.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, raised floor R-13, ceiling R=38 and walls R=13. Show the "R" values of floor insulation and the maximum "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/02/2018 SVALENZ1 OUT TO CUSTOMER Completed