Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM08026
Parcel: 10603079E

Address:
3202 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM08026
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 4; General Structural Notes (Foundations): The spread footing design references the IBC for allowable bearing values, then indicates to reference the soil report for additional information, and the soils engineer to inspect foundation excavations. Please coordinate. This is also indicated in the structural calculations.
2. Sheet 5; Isometric Plan A: A note at the spread footing indicates to reference Detail 4A for the footing. There is no Detail 4A on Sheet 6. Please verify.
3. Sheet 5; Isometric Plan A: A note at the roof indicates to reference Detail 10 for mid-span bracing. There is no Detail 10 on Sheet 6. Please verify.
4. Sheet 6 (Detail 1); Structural Calculations (Sheets 2.8 through 2.11): The calculations for the roof deck connections indicate #10 screws, while the detail indicates #12 screws. Please verify the screw size and spacing.
5. Sheet 6; Detail 4: Note A indicates to see Detail 4A for an optional spread footing. Please add that footing detail using the structural calculation Sheets 7.3 through 7.5.
6. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/09/2018 AVAUGHN1 OUT TO CUSTOMER Completed