Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM07895
Parcel: 107070230

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM07895
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/16/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The size of cleanouts must be the same as the pipe they service. You have a 3" cleanout for a 4" horizontal drain in one location and a 3" horizontal drain changing to a 4" horizontal drain without a 4" cleanout in another location. [Second comment: The sewer riser on P-1 calls for 4" waste downstream of the sand interceptor but the plumbing plan specified 3" waste. The size of cleanouts must be the same as the pipe they service.] [Initial comment: Explain the "existing 3" waste" shown on the sewer riser diagram.]
08/16/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/21/2019 DAVID RIVERA ZONING REVIEW Approved
08/27/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2019 AMARTIN1 OUT TO CUSTOMER Completed