Permit Number: T18CM07836
Parcel: 140062580

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T18CM07836
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2018 ANDREW CONNOR ZONING REVIEW Approved
10/03/2018 ACONNOR1 ENGINEERING REVIEW Passed
10/03/2018 ANDREW CONNOR NPPO REVIEW Passed
10/03/2018 GPERU1 BUILDING-RESIDENTIAL REVIEW Reqs Change The following comments are changes/additional information that is required on the construction plans.
1. A carbon monoxide detector is required because gas fuel is used for appliances. The CO detector must be installed outside of the sleeping areas in a central location in the hallway.
2. The gas yardline is undersized for the total BTU of the appliances and developed length of the gas line to the most remote location.
3. Need to show a framing plan for the replacement of roof rafters; show the size and spacing of rafters and insulation.