Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T18CM07828
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2019 | QJONES1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review | |
| 01/08/2019 | MCASTRO2 | NPPO | REVIEW | Passed | |
| 01/08/2019 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 11/28/2018 | NICHOLAS ROSS | ZONING | REVIEW | Needs Review | ZONING REVIEW TRANSMITTAL FROM: Nick Ross Lead Planner PROJECT: T18CM07828 3352 E. Hawthrone St Carport TRANSMITTAL: Date COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a). The DDO process may only be used to reduce the driveway length to a carport, and not to a garage (UDC Section 3.11.1.B.4). In a developing area, the minimum driveway length to the edge of a sidewalk for a carport is nineteen (19) feet (UDC Section 6.4.5.C.2.b.1). The minimum driveway length for a carport is eighteen feet to the property line (UDC Section 6.4.5.C.2.b.1.a & b). The proposed setback is 15ft. DDO is required. |