Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM07809
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/02/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
10/02/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
10/03/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S2.0: Please provide structural calculations for the revisions to the roof framing due to new mechanical loads. 2. Sheet a1.0; Detail 6: Please provide a vertical grab bar per the ICC/ANSI Figure 604.5.1. 3. Sheet a1.0; Floor Plan 1; Section 3; Detail 9: Please provide the wall stud spacing. 4. Sheet a1.0; Floor Plan 1: Is the roll up door indicated in the west wall in a new wall opening or an existing opening? Please verify. 5. General: Please provide written responses to all review comments. |
10/03/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/04/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/05/2018 | AVAUGHN1 | WATER | REVIEW | Completed | |
10/09/2018 | MASHFOR1 | FIRE | REVIEW | Approved | |
10/25/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the listing information for the proposed gas-fired appliances. Reference: Sections 301.3, 303.1, and 303.6, IFGC 2012. 2. Provide air for combustion, ventilation and dilution of the flue gases for the proposed water heater and roasters. Reference: Section 304, IFGC 2012. 3. Provide sediment traps for the gas-fired appliances. Reference: Section 408.4, IFGC 2012. 4. Provide venting for the water heater per the manufacturer's instructions. Reference: Section 503.2.3, IFGC 2012. 5. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 6. Coordinate the configuration of the drainage for the 3-compartment sink as shown in the riser diagram and as specified in the plumbing fixture schedule. Reference: Section 107.2.1, IBC 2012. |
10/26/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Alterations of an existing building in which the existing ceiling or wall cavities are exposed, shall have the exposed cavities filled with insulation. Reference: Section 101.4.3, IECC 2012. 2. Alterations to the building (e.g. new doors, lighting, etc.) shall comply with the current energy code. Provide a COMcheck envelope analysis of the alterations to the building. Reference: Sections C101.4.3 and C103, IECC 2012. 3. Provide the installation instructions for the proposed coffee roasters. Reference: Sections 301.3, 303.1, and 303.6, IFGC 2012. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/06/2018 | AVAUGHN1 | APPROVAL SHELF | Completed |
11/06/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
11/06/2018 | AVAUGHN1 | REJECT SHELF | Completed |