Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM07720
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/02/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/12/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. CV Specify the number of fixed seats for the determination of the occupant load. Keynote 1 on sheet A1.0 indicates that seating will be under a separate permit? Please remove the keynote and provide a final seating plan for indoor and outdoor seating. Provide DÉCOR PACKAGE called out on the OCCUPANCY ALLOWANCE LEGEND. IBC 1004.4 2. A1.0 Keynote 26. Revise keynote to read: Door closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to an open position of 12 degrees shall be 5 seconds minimum. ICC A117.1 3. A1.0 Accessible dining surfaces. At least 5 percent, but not less than 1 of the dining surfaces for seating, or standing spaces, shall be accessible and be distributed throughout the eating area. Show designated accessible dining locations to include outdoor dining areas. IBC 1108.2.9.1 4. A1.0 Detail 4: Specify the size/type of fasteners for anchorage of new walls/partitions to the floor slab. Specify the size of wall diagonal bracing and fasteners to the roof supports and walls/partitions. IBC 1607.5. 5. SD 4 Drive thru canopy base detail must be constructed to withstand 115 mile per hour wind zone; not 90 MPH as noted on the detail. Please revise to reflect correct wind zone. IBC FIG 1609. Please submit written responses to all plan review comments. SD 4 Drive thru canopy base detail must be constructed to withstand 115 mile per hour wind zone; not 90 MPH as noted on the detail. Please revise to reflect correct wind zone. IBC FIG 1609 |
10/15/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
10/15/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the temperature of the tempered water supply to the public lavatories is controlled using a thermostatic mixing valve listed to ASSE 1070. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012. |
10/15/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/24/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref; Plan Sheet E0.1, E2.0, E2.1, E3.0B. #1. Per the building lighting plans, it appears that there are more than 3 new or retrofitted exterior luminaires proposed to be installed for this project. Therefore, the exception 102.4.2 stated per the Flag Note #9 would not apply. Provide a complete lumen calc, including the existing parking lot lighting. Identify any existing lighting with a mark that correlates with the lumen calcs and luminaire schedule. #2. Provide lighting manufacturer cut sheets to verify shielding and color output temperature. #3. Show how the exterior unshielded luminaires curfew is controlled. #4. Provide a note on the plans stating that a special inspection for outdoor lighting is required. Sec. 105.2.2, 106.2.1. Ref; 2011 NEC 110.26D, 2012 IBC sec 107.2.1 |
10/24/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Needs Review | DP must be approved first. |
10/25/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Site Section Manager PROJECT: 9490 E. Golf Links Road - Remodel T18CM07720 Building Plan (1st Review) TRANSMITTAL DATE: October 25, 2018 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plan set for compliance with DP18-0248 and it appears that the building plans are in compliance, but until the DP18-0248 is approved Zoning cannot approve until the building plans. 3. Until all other PDSD review agencies have approved the building plans Zoning cannot approve. Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
10/25/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Site Section Manager PROJECT: 9490 E. Golf Links Road - Remodel T18CM07720 Building Plan (1st Review) TRANSMITTAL DATE: October 25, 2018 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plan set for compliance with DP18-0248 and it appears that the building plans are in compliance, but until the DP18-0248 is approved Zoning cannot approve until the building plans. 3. Until all other PDSD review agencies have approved the building plans Zoning cannot approve. Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/05/2018 | QJONES1 | APPROVAL SHELF | Completed |
11/05/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
11/05/2018 | QJONES1 | REJECT SHELF | Completed |