Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM07703
Parcel: 110113620

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM07703
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please revise the APPLICABLE CODES to the 2012 International Building, Mechanical, Plumbing, Energy Conservation and Fire Code, and 2009 ICC A117.1 ANSI Standard.
10/10/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also, provide a written response.
As per the last electrical plan review comment, it was requested to provide compliance with NEC art 408.4, for branch circuit identification. Please update the panel schedule accordingly. "Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all others"….. "No circuit shall be described in a manner that depends on transient conditions of occupancy".
Also the correct electrical code is 2011 NEC, see title sheet.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4.
10/10/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revised sheet M2.01 was not submitted.
2. Provide a ventilation analysis for the area being revised. Analysis shall include the balancing data for the existing RTU (e.g. CFM for each diffuser and total amount of outside air for the RTU).

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2018 QJONES1 APPROVAL SHELF Completed
10/26/2018 QJONES1 OUT TO CUSTOMER Completed
10/26/2018 QJONES1 REJECT SHELF Completed