Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM07703
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/10/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please revise the APPLICABLE CODES to the 2012 International Building, Mechanical, Plumbing, Energy Conservation and Fire Code, and 2009 ICC A117.1 ANSI Standard. |
| 10/10/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also, provide a written response. As per the last electrical plan review comment, it was requested to provide compliance with NEC art 408.4, for branch circuit identification. Please update the panel schedule accordingly. "Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all others"….. "No circuit shall be described in a manner that depends on transient conditions of occupancy". Also the correct electrical code is 2011 NEC, see title sheet. Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4. |
| 10/10/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revised sheet M2.01 was not submitted. 2. Provide a ventilation analysis for the area being revised. Analysis shall include the balancing data for the existing RTU (e.g. CFM for each diffuser and total amount of outside air for the RTU). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 10/26/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 10/26/2018 | QJONES1 | REJECT SHELF | Completed |