Permit Number: T18CM07563
Parcel: 11705033A

Address:
340 E 6TH ST

Review Status: Active

Review Details: POST 3RD PARTY REVIEW

Permit Number - T18CM07563
Review Name: POST 3RD PARTY REVIEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2019 MROSS2 FIRE REVIEW Approved
12/05/2019 DAVID RIVERA ZONING REVIEW Approv-Cond pending approval by the design professional.
12/05/2019 ROBERT SHERRY WATER REVIEW Completed
12/09/2019 LOREN MAKUS ENGINEERING REVIEW Approved
12/12/2019 MGAYOSS1 DESIGN PROFESSIONAL REVIEW Approved DATE: December 11, 2019
TO: City of Tucson Planning & Development Services Department
FROM: Corky Poster, Design Professional
RE: Union on 6th, COT #T18CM07563 and #T19CM05174
Reviews of Permit Drawings for Conformance with IID Design Approval
OWNER REP: a.23studios
1. On A3E.1 East elevation 1 shows the 2nd and 3rd floor window protrusions merged into a single
volume. This is different from an earlier version, but as stated earlier, this is a minor and
satisfactory elevation change. APPROVED.
2. The porcelain tile (non-decorative) size on the design rendering is shown as 4” or 6”. On the
permit set (A3E.1) those tiles are shown as 18”. The recommendation was to return to the
smaller scale. The architect has hand-noted on sheet A3E.1 that the 18” tiles shall be cut to 6”.
That change back to 6” as documented by the note is a satisfactory solution and is APPROVED.
3. It was pointed out by the DP that the mural was not shown on A3W.2. It was explained that this
mural will be accomplished by a yet-to-be-selected artist. According to the a23 studios architect,
“The mural will be formally submitted to the City of Tucson.” This explanation is accepted. Please
notify the DP and P&DSD when the mural submission is made.
4. It was recommended by the DP that a planter be built on the 2nd level terrace on the SE corner of
the building on 4th Avenue so that the residents and/or guests using that terrace would not be
able to physically overlook 4th Avenue. A planter is shown on A1E.3 in the shaded area with the
note “3’-0” line of planters.” It is also shown on A0E.3. It is also shown on DP18-0067 p.8 of 9 L7.2
of the Landscape Plan. This accommodation of my request is satisfactory and is APPROVED.
Thank you.

On Jan 7, 2020, at 10:57 AM, Corky Poster <cposter@pmm.design> wrote:
Yes. I think eliminating the stair windows (from an elevation point of view) is an improvement. Having windows in a staircase that match windows into a unit is not a good idea. You already don’t have natural light in the other stair core, so I think this is consistent. And I like the color change.
So all good…….Yes, this is an acceptable modification. (And I very much appreciate your efforts to keep me updated on changes.)
Corky Poster
520.861.6320
PMM ? POSTER MIRTO McDONALD
From: Benjamin Cole <ben@a23studios.com> Sent: Monday,
January 6, 2020 12:31 PMTo: Corky Poster <cposter@pmm.design>Cc: Burak Bekat <burak@a23studios.com>Subject: Union on 6th
Hi Corky -
Happy New Year!
Please see attached West Building / West Elevation at Union on 6th.
Our Southwest stair core is shown with windows that align horizontally with adjacent windows. Reality is the stair landings will fall in the middle of those windows.
We’d like to
? Eliminate the windows in that core and change the stucco color to the lighter tone. This would then match the Northwest stair core / West Elevation (SW core already has a higher parapet condition to match NW).
Is this an acceptable modification?
Also considered:
? Shifting the windows up / down to align properly with the landings but that created a unique horizontal mis-alignment on the elevation.
? A spandrel glass solution with windows staying put but that would create a unique glass look and windows would not function well form inside.
Please let us know if you have any questions or would like to discuss. Feel free to call me at 850-9012 anytime if so.
Thanks!
Ben
12/31/2019 PMARTIN1 HC SITE REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2020 SBORZAK1 OUT TO CUSTOMER Completed